CVE-2025-27257
Insufficient Verification of Data Authenticity vulnerability in GE Vernova UR IED family devices allows an authenticated user to install a modified firmware.The firmware signature verification is enforced only on the client-side dedicated software Enervista UR Setup, allowing the integration check to be bypassed.
An authenticated attacker can install a malicious firmware on a vulnerable device
March 7, 2025
This issue affect the GE Vernova UR IED device family from version 7.0 to 8.60
CVE-2025-27257
CVSS:3.1/AV:A/AC:L/PR:H/UI:N/S:U/C:N/I:H/A:H
6.1
Update the firmware of affected devices to the latest released version
Diego Giubertoni of Nozomi Networks
Curated and maintained by Nozomi Networks Labs, the Threat Intelligence™ service provides threat and vulnerability updates to Guardian, making it easy for IT/OT professionals to stay on top of current OT and IoT risks.
Learn more“Threat actors love finding new ways to attack critical infrastructure. We love finding new ways to detect their malware before damage occurs.”
TRITON is the first known cyberattack that directly interacted with a Safety Instrumented System (SIS). Labs reverse engineered the TriStation suite of software and delivered a report and two free tools for security researchers. This research was presented at Black Hat USA 2018.
The Labs team reverse engineered the GreyEnergy malicious document (maldoc) that leads to the installation of the malware (backdoor) on a victim’s network. Project outcomes include a report, multiple blogs and two free tools for security researchers.
IEC Working Group 15 (WG15) is developing technology standards for secure-by-design power systems. Labs contributes to the standards and has demonstrated how they can be used to identify hard-to-detect cyberattacks. Research from this effort was presented at Black Hat USA 2019.